Honeywell T775L2007/U Electronic Remote Temperature Controller

HONT775L2007 MFG #: T775L2007/U
  • Control Range: -40 to 248 deg F
  • Differential: 1 to 150 deg F
  • Domestic / Import: Import
  • Switch Action: SPDT
  • Switch Type: Relay
  • Dimensions: 4-13/32 in W x 2-15/16 in D x 8-5/32 in H
  • Enclosure Type: NEMA 1
  • Manufacturer: Honeywell
  • Manufacturer #: T775L2007/U
  • Number of Relay Inputs: 2
  • Number of Relay Outputs: 4
  • Sensing Bulb Size: 1/4 in Dia x 2 in L
  • Sensor Type: 1097 Ohm PTC at 77 deg F
  • Series: T775
  • Voltage Rating: 24/120/240 VAC
T775 electronic remote temperature controller, is the next generation in commercial/agricultural control - capable of remote sensing temperature, humidity, pressure, etc., and providing switched and/or proportional outputs to various types of loads.

Electronic Remote Temperature Controller, Series: T775, -40 to 248 deg F Control Range, 1 to 150 deg F Differential, SPDT, Relay Switch, 1097 Ohm PTC at 77 deg F Sensor, 1/4 in Dia x 2 in L Sensing Bulb, 2 Relay Inputs, 4 Relay Outputs, 24/120/240 VAC, NEMA 1, 4-13/32 in W x 2-15/16 in D x 8-5/32 in H, Import
  • Features
  • Universal model (T775U) can control pressure, humidity, or any variable analog input, special boiler model (T775P) for boiler control
  • Special staged sequencing model (T775L) for sequence staging of relays with one or two set points
  • Special expansion model (T775S) for staging up to 12 relays with two set points (each T775S provides 4 relays)
  • Save time on installations with the easy-to-use graphical interface, large display and the intuitive programming
  • Provide very fast or very fast response times on modulating outputs by adjusting the integral and derivative times (PI or PID)
  • Configure models with reset in a few easy steps
  • Use the T775L and T775P to stage up to 12 relays (with optional T775S) from two independent heat or cool set points
  • Support for digital output alarm on the T775P configurable based on minimum, maximum or differential temperature
  • 50/60 Hz frequency
  • Output - relay with reset
  • Analog output - Electronic series 90, 4 to 20 mA, 0 to 10 VDC, 2 to 10 VDC
  • Relay contact - 24 VAC - 10.0A resistive, 120 VAC - 1/2 hp, 9.8 FLA, 58.8 LRA, 125 VA pilot duty, 240 VAC - 1/2 hp, 4.9 FLA, 29.4 LRA, 125 VA pilot duty
  • Sensors included - 50021579-001 (1)
  • Maximum distance to sensor up to 1000 ft
  • +/- 1 deg F at 77 deg F accuracy
  • 1 to 150 deg F throttling