- Interrupts power immediately in a low water condition. Burner circuit locks-out if water remains below probe for 30 seconds. Manual reset will not trip due to power failures. Test button checks burner circuit to ensure proper control operation and lock-out function without lowering the water level. Note: Can also be used as a secondary cut-off on steam boilers.
Hydrolevel Safgard™ Low Water Cut-Off, Series: 500, 120 VAC, 160 psi, Manual Reset, 4 VA
- Burner circuit test button
- LED indicating lights
- Meets ASME CSD-1 requirements for commercial water boilers
- Flexible design
- Easy installation
- Pressure Rating160 psiReset TypeManualVoltage Rating120 VACManufacturerHydrolevelManufacturer #45-550Power Rating4 VASeries500